Power System Analysis And Design SI Edition 6Th Edition By Glover - Test Bank
Quiz 1
ECE 476
Two balanced three-phase loads are in parallel.
a. b. Load 1 draws 10 kW at 0.8 PF lagging
Load 2 draws 20 kVA at 0.6 PF leading
The loads are supplied by a balanced three-phase 480 VLL source.
(a) Draw the power triangle for the combined load.
PL = P1 + P2 = 22 kW
21.12Β°
QL = Q1 + Q2
= -8.5 kVAR
SL = 23.59
kVA
(b) Determine PF of the combined load.
cos21.12Β° = 0.933 leading
(c) Determine the magnitude of the line current from the source.
ππΏ
=
23.59Γ103
= 28.37 π΄
πΌπΏ =
β3ππΏπΏ
β3Γ480
(d) Y-connected inductors are now installed in parallel with the combined load. What value of
inductive reactance is needed in each leg of the Y to make the source power factor unity?
3(ππΏπ)2
ππΌππ = |ππΏ| = 8.5 Γ 103 ππ΄π =
3(480/β3)2
πY =
= 27.1 Ξ©